Judul/Title Reactive Power Control Modes in Smart Inverters for Overvoltage Mitigation: Impacts on LVRT Performance—-A Case Study in Gorontalo, Indonesia
Penulis/Author Muammar Zainuddin (1); Dr. Ir. Mokhammad Isnaeni Bambang Setyonegoro, M.T. (2); Ir. Eka Firmansyah, S.T., M.Eng., Ph.D., IPM. (3); Prof. Ir. Tumiran, M.Eng., Ph.D. (4)
Tanggal/Date 28 2025
Kata Kunci/Keyword
Abstrak/Abstract The increasing penetration of photovoltaic (PV) power generation into distribution networks presents an overvoltage challenge during normal operations. Smart inverter reactive power control modes are promising solutions to address this challenge. To mitigate overvoltage, reactive power control modes are commonly configured with conservative limits to protect equipment. However, during severe faults, a higher reactive current availability is required to comply with low-voltage ride-through (LVRT) requirements. Therefore, reactive power control modes should be capable of operating under both normal and fault conditions. This study investigated how the standard reactive power control modes used for overvoltage mitigation affected the LVRT performance. A case study was conducted on a 2 MWp PV plant connected to a real medium-voltage feeder in Gorontalo, Indonesia, which experienced overvoltage during peak PV injection. To assess this impact, a multifunctional control framework was developed that integrated a reactive power controller (Fixed VAr, Fixed power factor, Watt–VAr, and Volt–VAr), fault detection logic, an LVRT mechanism, and a current limiting scheme. Three-phase symmetrical faults were simulated with variations in the reactive power limits, voltage sag depths, and delayed fault clearing. The results revealed a clear trade-off: tighter reactive power limits effectively mitigated steady-state overvoltage but impaired LVRT performance by reducing reactive current injection and delaying voltage recovery. Furthermore, each control mode exhibited distinct dynamic behaviors, indicating different parameter-setting priorities. These findings underscore the need to configure reactive power limits and firmware parameters to sustain overvoltage mitigation during normal operation, while preserving LVRT during faults.
Rumpun Ilmu Teknik Elektro
Bahasa Asli/Original Language English
Level Internasional
Status
Dokumen Karya
No Judul Tipe Dokumen Aksi
1FULL ARTIKEL_M_ ISNAENI BAMBANG SETYONEGORO_IEEE ACCESS.pdf[PAK] Full Dokumen
2CEK TURNITIN.pdf[PAK] Cek Similarity