Karya
Judul/Title Pengaruh Resistans Busur Pada Unjuk Kerja Rele Jarak pada Transmisi 150 kV
Penulis/Author Ir. Bambang Sugiyantoro, MT (1) ; HASAN KURNIAWAN (2); Ir. Harnoko Stephanus, M.T. (3); RR Eny Sukani Rahayu, S.T., M.Eng. (4)
Tanggal/Date 2017
Kata Kunci/Keyword
Abstrak/Abstract A transmission line plays an important role in an electric power system to distribute electricity from power plants to substations. Distance relay as the primary protection of the transmission line serves to isolate faults. Arc resistance emerged during faults may affect the performance of the distance relay. Distance relay even can work incorrectly due to a mistake in identifying the faults.The purpose of this study is to determine the effect of fault arc on the transmission line to the performance of distance relay at transmission line 150 kV. In this research, modeling system used NEPLAN software. Then, short circuit simulation in the area around the tip of zone one protection was conducted to determine the value of the arc resistance using Warrington equation. Simulation results of the distance relay performance with arc resistance were compared to those without the resistance. The simulation results showed that the arc resistance could reduce the effectiveness of distance relay to protect the transmission line. In one phase to ground faults, the reach of the zone one protection was approximately 74% out of 80%. While in two and three phases to ground faults, it was about 76% out of 80%.
Level Nasional
Status
Dokumen Karya
No Judul Tipe Dokumen Aksi
1Pengaruh Resistans Busur_compressed (1).pdf[PAK] Full Dokumen